This website uses non-intrusive cookies to improve your user experience. You can visit our cookie privacy page for more information.

Notices served

Notice 312523604 served against Dana Petroleum (E&P) Limited on 08/06/2022
Notice Type Improvement Notice
Description That you have failed to ensure that the risk of exposure of your employees and others to substances hazardous to health (namely legionella bacteria) is either prevented or, where this is not reasonably practicable, adequately controlled in that no written scheme for controlling the risk to legionella bacteria exists for Triton FPSO and that you could not demonstrate prevention and control arrangements detailed in Dana procedure UK-UK-HS-HEA-STD-0004 (Managing Water Quality and risks from Legionella) are replicated in the actual working practices onboard the installation. Specific examples include but are not limited to; Potable Water bunkering hose management compliance gaps, visual internal hot and cold water tank inspections not being undertaken on an annual basis and calorifier temperature control being found out of specification limits. Further to this you have failed to begin to undertake improvement actions recommended within the 2019 Legionella risk assessment.
Compliance Date 28/10/2022 Revised Compliance Date 13/01/2023
Result Complied with

Breaches involved in this Notice

Location of Offence
Address Triton/Dana Petroleum (E&P) Li
78 Cannon Street
LONDON
EC4N 6AF
Region
Local Authority Not Applicable
Industry Extractive and utility supply industries
Main Activity 06100 - EXTRACTION OF CRUDE PETROLEUM
Type of Location Offshore Safety Directive Regulator
HSE Details
HSE Group EDU5INHY HSE Directorate Energy Division
HSE Area HSE Division
Updated: 2020-03-04