Notice 312136903 served against Sappi Rockwell Solutions Limited on 22/12/2021
Notice Type Improvement Notice
Description 312136614 - You have failed to ensure that the risk of fire and / or explosion is either eliminated or reduced so far as is reasonably practicable in that the vent for Mixing Tank L terminates inside Mixing Room 2 and therefore there is the risk of flammable and / or explosive atmospheres forming in the mixing room and the potential for a fire and / or explosion to occur resulting in serious injury or death. 312136678 - You have failed to ensure that the risk of fire and / or explosion is either eliminated or reduced so far as is reasonably practicable in that the vent for Mixing Tank M terminates inside Mixing Room 2 and therefore there is the risk of flammable and / or explosive atmospheres forming in the mixing room and the potential for a fire and / or explosion to occur resulting in serious injury or death. 312136775 - You have failed to ensure that the risk of fire and / or explosion is either eliminated or reduced so far as is reasonably practicable in that the vent for Mixing Tank N terminates inside Mixing Room 2 and therefore there is the risk of flammable and / or explosive atmospheres forming in the mixing room and the potential for a fire and / or explosion to occur resulting in serious injury or death. 312136794 - You have failed to ensure that the risk of fire and / or explosion is either eliminated or reduced so far as is reasonably practicable in that the vent for Mixing Tank Q terminates inside Mixing Room 2 and therefore there is the risk of flammable and / or explosive atmospheres forming in the mixing room and the potential for a fire and / or explosion to occur resulting in serious injury or death. 312136844 - You have failed to ensure that the risk of fire and / or explosion is either eliminated or reduced so far as is reasonably practicable in that the vent for Mixing Tank R terminates inside Mixing Room 2 and therefore there is the risk of flammable and / or explosive atmospheres forming in the mixing room and the potential for a fire and / or explosion to occur resulting in serious injury or death. 312136899 - You have failed to ensure that the risk of fire and / or explosion is either eliminated or reduced so far as is reasonably practicable in that the vent for Mixing Tank S terminates inside Mixing Room 2 and therefore there is the risk of flammable and / or explosive atmospheres forming in the mixing room and the potential for a fire and / or explosion to occur resulting in serious injury or death. 312136900 - You have failed to ensure that the risk of fire and / or explosion is either eliminated or reduced so far as is reasonably practicable in Mixing Room 1. Specifically, you have failed to provide adequate local exhaust ventilation, suitably positioned, to prevent or minimise potentially unsafe concentrations of flammable and/or explosive vapours into Mixing Room 1 when flammable liquid product (above flashpoint of solvents and at temperatures above ambient) is pumped or emptied by gravity out of mixing tanks into drums. 312136903 - You have failed to ensure that the risk of fire and / or explosion is either eliminated or reduced so far as is reasonably practicable in Mixing Room 2. Specifically, you have failed to provide adequate local exhaust ventilation, suitably positioned, to prevent or minimise potentially unsafe concentrations of flammable and/or explosive vapours into Mixing Room 2 when flammable liquid product (above flashpoint of solvents and at temperatures above ambient) is pumped or emptied by gravity out of mixing tanks into drums. 312136912 - You have failed to make a suitable and sufficient assessment of the risks to employees which arise from dangerous substances which are, or are liable to be, present at the workplace.
Compliance Date 03/03/2022 Revised Compliance Date 01/09/2022
Result Complied with

Breaches involved in this Notice

Related Notices

Location of Offence
Address Wester Gourdie Ind Est/Rockwel
Brunel Road
DUNDEE
DD2 4TG
Scotland
Region Scotland
Local Authority Dundee UA
Industry Manufacturing
Main Activity 22220 - MF OF PLASTIC PACKING GOODS
Type of Location Fixed
HSE Details
HSE Group FODOP1GP2 HSE Directorate Field Operations Division
HSE Area HSE Division Scotland
Updated: 2020-03-04