This website uses non-intrusive cookies to improve your user experience. You can visit our cookie privacy page for more information.

Notices served

Notice 312071634 served against Perenco UK Limited on 29/11/2021
Notice Type Improvement Notice
Description During my inspection of ST3 I identified that there was no provision to close the Export Pipeline Emergency Shut Down Valve (ESDV) local to the ESDV. Therefore you have failed to ensure that the requirements contained in Schedule 3 are complied with in relation to the export pipeline from ST3, namely that the ESDV is capable of being closed by a person positioned by it. My inspection also revealed that the nearest ESDV control point was on the mezzanine deck located within the Hydraulic Power Unit (HPU). My inspection also revealed that labelling of equipment such as riser ESDVs and stop buttons did not allow for straight forward identification for the work equipment in question. ESDV Control Panels were located on a separate deck behind cabinet doors which required the opening of the doors to establish which work equipment the panels were associated with. Furthermore the Push button on the main deck had no labelling to indicate this would initiate an ESD shutdown. PUWER Regulation 23 requires that every employer shall ensure that work equipment is marked in a clearly visible manner with any marking appropriate for reasons of health and safety.
Compliance Date 29/05/2022 Revised Compliance Date
Result Complied with

Breaches involved in this Notice

Location of Offence
Address Ravenspurn North ST3/Perenco U
8 Hanover Square
LONDON
W1S 1HQ
Region
Local Authority Not Applicable
Industry Extractive and utility supply industries
Main Activity 06100 - EXTRACTION OF CRUDE PETROLEUM
Type of Location Fixed N.U.I.
HSE Details
HSE Group EDU5S2 HSE Directorate Energy Division
HSE Area HSE Division
Updated: 2020-03-04