This website uses non-intrusive cookies to improve your user experience. You can visit our cookie privacy page for more information.

Notices served

Notice 309947111 served against ExxonMobil Chemical Limited on 27/06/2019
Notice Type Improvement Notice
Description You have failed to take all measures necessary to ensure that the DMS bubbler drum K-D-02B is fit for continued service in that you have not carried out the inspector's recommended action to remove all insulation and carry out a CUI inspection of the vessel shell, despite significant insulation damage and an ongoing steam leak beneath the insulation.
Compliance Date 19/09/2019 Revised Compliance Date 01/12/2019
Result Complied with

Breaches involved in this Notice

Location of Offence
Address Fife Ethylene Plant Mossmorran
Beverkae House
Mossmorran
COWDENBEATH
Fife
KY4 8EP
Scotland
Region Scotland
Local Authority Fife UA
Industry Manufacturing
Main Activity 20590 - MF CHEMICAL PRODUCTS NEC
Type of Location Fixed
HSE Details
HSE Group CEMHDU1F HSE Directorate Chemical Explo & Microbio Hazards Division
HSE Area HSE Division Scotland
Updated: 2020-03-04